Current consumption in relation to the input voltage
Voltage type
DC
Input voltage
24 V
Input current
11 A
DC input voltage range
28 ... 58 V DC
Input fuse (internal)
20A T
Input voltage, max.
34 V
Input voltage, min.
18 V
Inrush current
<4 A @ Nominal input voltage
Rated input voltage
24 V DC
Recommended back-up fuse
15 A (DI) / 10A…16A (Char. B, C)
Wire connection method
Screw connection
Output
Capacitive load
unrestricted
Connection system
Screw connection
Continuous output current @ UNominal
5 A @ 60°C, 6.25 A @ 45°C, 3.75 A @ 70°C
DCL - peak load reserve
Multiple of the rated current
600 %
Boost duration
15 ms
Mains failure bridge-over time
Mains failure bridge-over time, min.
10 ms
Input voltage type
DC
Input voltage
24 V
Output current
5 A
Output voltage
48 V
Nominal output current for Unom
5 A @ 60 °C
Output power
240 W
Output voltage, max.
56 V
Output voltage, min.
28.5 V
Output voltage, note
(adjustable via potentiometer on front)
Overload protection
Yes
Parallel connection option
yes, max. 3
Protection against inverse voltage
Yes
Rated output voltage
48 V DC
Residual ripple, breaking spikes
≤ 50 mVPP @full load
Wire connection method
Screw connection
General data
Adjacent
No
Current limiting
150% Iout
Degree of efficiency
> 90 %
Mounting position, installation notice
On TS 35 mounting rail, 50 mm clearance above and below for free air supply., With a load ≥ 50 % of the rated current, keep at least 15 mm lateral spacing., The device should be mounted vertically. For other mounting directions, derating to 75% of the load must be considered.